The Extech 48VFL11 Temperature PID Controller includes fuzzy logic enhanced PID and a soft start feature to prevent heaters from cold starts. PID plus fuzzy logic can handle even the most demanding applications, reducing overshoot, undesirable process variations, and drift. The gentle start function is appropriate for operations used in the thermoplastics industry, which need careful, precise, and slow heating of the product. It supports thermocouple and RTD inputs. Includes a single stage ramp and soak program with a ramp-to-set point limit that can be used with the soft start feature to meet essential process demands. Complete with mounting bracket hardware and screw terminals for simple wiring. Also available with a 4-20 mA output (48VFL 13).
Specifications | ||
---|---|---|
Inputs | Type K | -58 to 2498°F (-50 to 1370°C) |
Type J | -58 to 1832°F (-50 to 1000°C) | |
Type B | 32 to 3272°F ( 0 to 1800°C) | |
Type T | -454 to 752°F (-270 to 400°C) | |
Type E | -58 to 1382°F (-50 to 750°C) | |
Type R or S | 32 to 3182°F ( 0 to 1750°C) | |
Type N | -58 to 2372°F (-50 to 1300°C) | |
Type C | -58 to 3272°F (-50 to 1800°C)) | |
PT100Ω RTD (DIN) | -328 to 1652°F (-200 to 850°C) | |
PT100Ω RTD (JIS) | -328 to 1202°F (-200 to 650°C) | |
Control/Alarm Relay | 5 Amp @ 110V, SPST (resistive load) | |
DC Current Output | 4-20mA (resistive); Impedance 600 ohms | |
Accuracy | Thermocouple: ±1.8°F (1ºC); RTD: ±0.36°F (0.2ºC) | |
Sampling Time | Four (4) samples per second | |
LED Display | Two 4-digit displays for Process Value, Setpoint, and programming modes | |
LED Status | Alarm and Control output status | |
Control Modes | Fuzzy Logic enhanced three-term PID with Auto Tune | |
• Proportional Band 0 to 300.0% | ||
• Integral time 0 to 3600 seconds | ||
• Derivative time 0 to 900 seconds | ||
• Hysteresis 0.0 to 200.0 or 0.0 to 2000 | ||
• Cycle time 1 to 100 seconds | ||
Front Panel | Lexan construction, Drip/Dust proof; IR rating: IEC IP63 | |
Power Supply | 90 to 264 VAC; 50/60 Hz (5VA power consumption) |