FLIR DM286 Industrial Thermal Imaging Multimeter with IGM™
Industrial Thermal Imaging Multimeter with IGM™

The FLIR DM286 industrial imaging multimeter is the ideal instrument for electrical inspectors looking for a safe, precise, and efficient approach to detect, document, and discuss results. IGM™ (Infrared Guided Measurement) and MSX® (Multi-Spectral Dynamic Imaging) allow for safe identification of potential risks before making contact. The powerful multimeter can collect and save up to 30,000 pictures and 100 log files, as well as record thermal and visual video clips. Stream real-time data from the DM286 to your mobile device. The METERLiNK® app allows you to quickly and easily collect readings, photos, and videos for analysis, trending, and sharing.

Specifications

IR Resolution 160 × 120 (19,200 pixels)
Display Counts 6000
AC/DC Voltage 1000 V AC RMS ±(1.0%+3) 1000 V DC ±(0.09%+3)
AC/DC Amps 10.00 A AC RMS ±(1.5%+3) 10.00 A DC ±(1.0%+3)
Connectivity Bluetooth BLE
Color Palettes Iron, rainbow, arctic, white hot, and black hot
Field of view - visual 71° × 56°
Focus Fixed
Frame Rate 9 Hz
Image Modes Thermal MSX (Multi Spectral Dynamic Imaging)
Thermal Camera only
Digital Camera only
IR Resolution 160 × 120 (19,200 pixels)
IR Sensitivity 150 mK (0.15°C)
Spectral Response 8–14 µm
Thermal Imaging Detector FLIR Lepton® microbolometer
Visual Focus and FOV Fixed focus, 71° × 56° FOV
Visual Resolution 2 MP (1600 × 1200 pixels)
AC/DC Amps 10.00 A AC RMS ±(1.5%+3) 10.00 A DC ±(1.0%+3)
AC/DC LoZ V 1000 V AC RMS or 1000 V DC ±(1.3%+4)
AC/DC mVolt AC 600.0 mV ±(1.0%+3) DC 600.0 mV±(0.2%+3)
AC/DC Voltage 1000 V AC RMS ±(1.0%+3) 1000 V DC ±(0.09%+3)
Calibration Cycle Once per year, recommended
Capacitance 10.00 mF ±(4.0%+5)
Continuity check threshold 10–100Ω
Diode Test 1.500 V ± 0.9%
Display Counts 6000
Frequency Counter 100.00 kHz ±(0.1%+5)
Measuring Rate 3 samples per second
Resistance 6.000 MΩ ±(0.9%+5), 60.00 MΩ ±(3.0%+5)
Temperature Accuracy ±3°C (5.4°F) or ± 3% of the reading (whichever is greater) for temperatures > 25°C (77°F) ±5°C for temperatures -10°C to 25°C (14°F to 77°F)
Temperature Range –5°C to 300°C (23°F to 572°F)
Temperature Resolution 0.1°C (0.1°F)
Temperature Type K thermocouple -40°C to 400°C DMM ± (1.0% + 3°C) / IGM ± (1.0% + 5°C)
(-40°F to 752°F DMM ± (1.0% + 5.4°F) / IGM ± (1.0% + 9°F)
Thermal Sensitivity 150 mK (0.15°C)
VFD AC V: 1000 V AC RMS, ±(1.3%+4) at 45∽65 Hz
Communication Protocol METERLiNK
Connectivity Bluetooth BLE
Image File Format Radiometric
Storage 40,000 readings per memory set
Storage Media eMMC 4GB
Stored Image Capacity up to 30,000
Video Recording 50 minutes maximum duration
20 seconds max duration for file transmission
Display 2.8"
Display Brightness High, Medium, Low
Auto Power Off For Meter: set to OFF, 2, 5, or 10 minutes
For Worklight only: set to OFF, 5, 15, or 30 minutes
Battery TA04, Lithium Polymer Rechargeable, 3050 mAh. Two supplied.
Battery life Approx. 6.5 hours in IGM mode with display brightness set to medium.
Approx. 10 hours in Multimeter mode (medium brightness)
Non_Contact Voltage Detector [NCV] Yes
Dimensions (L x W x H) 20 cm × 9.6 cm × 5.6 cm (7.9 in × 3.8 in × 2.2 in)
Included 1 x DM286 Industrial Thermal Imaging Multimeter
1 set of CATIV 600V Test Lead
1 set of CATIV 600V Alligator Clip
1 x Type-A to Micro-USB Cable (with Data transfer capability)
1 x K-type Thermocouple (-30°C to 260°C)
1 x Soft-sided carrying case
1 x FLIR Quick Start Guide
1 x FLIR Warranty Card
2 x TA04 Rechargeable Battery Cell
Scanning Mode Continuous scan. Crosshairs and laser pointer targeting.
Weight 569 g (1.25 lb) without battery (approx.)
Worklights x1 LED
Certifications ETL, FCC, CE, RCM, UKCA, FDA, EN60825, EN50689
Drop test 2 m (6.6 ft)
EMC EN61326-1
Emissivity Settings 0.10 to 1.00 (default is 0.95); select from four presets or set manually.
IP Rating IP40
Laser Pointer Power ≤0.39 mW
Laser Type Class I (red)
Laser Wavelength 640 nm to 660 nm
Operating Altitude 2000 m (6560 ft)
Operating Temp & Humidity -10°C to 30°C (14°F to 86°F), <85% RH
30°C to 40°C (86°F to 104°F), <75% RH
40°C to 50°C (104°F to 122°F), <45% RH
Pollution Degree 2.0
Safety IEC 61010-1 CAT IV - 600 V, CAT III - 1000 V
Storage temperature and relative humidity [RH] -20°C to 60°C (-4°F to 140°F), 0–80% RH (without batteries)
Warranty Limited 10-Year Warranty https://www.flir.com/testwarranty
Software FLIR METERLiNK® app